The addressable Input/Output module is a fully monitored device which permits the interfacing of third-party equipment with the fire alarm control panel using normally open dry contact connections, while also providing a changeover output relay to control ancillary equipment.
The interface is used to monitor the contacts of an external system which must be interfaced to the fire alarm system, for example a flow switch in a sprinkler system.
The output relay can be programmed to close fire doors, activate smoke removal systems, etc.
SUPPLY VOLTAGE |
Loop Powered – 17V to 30V DC |
LOOP CURRENT – QUIESCENT |
I/P: OK 0.46 mA – FLT OC 0.33 mA – FLT SC 0.79 mA |
LOOP CURRENT – ALARM LED ILLUMINATED |
2.0 mA +9.8 mA with Relay Active |
MAX. CABLE SIZE |
2.5 mm² |
PROTECTION |
IP43 |
OPERATING TEMPERATURE |
-10ºC to 50ºC |
MAX. HUMIDITY |
95% RH Non-Condensing |
MATERIAL |
ABS |
ENCLOSURE |
White or Red |
DIMENSIONS |
100 (D) x 48 (H) mm |
WEIGHT |
Module: 29 g / Module + box: 134 g |
آموت